Welcome Customer !

Membership

Help

Shanghai Tianbi Electric Technology Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products
Product Categories

Shanghai Tianbi Electric Technology Co., Ltd

  • E-mail

  • Phone

  • Address

    Room 119, Building A, No. 58 Zhuwei Road, Zhuxing Town, Jinshan District, Shanghai

Contact Now

Guodian Nanrui NSR641RF-DT backup power automatic switching device

NegotiableUpdate on 05/06
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The NSR641RF-DT backup power supply automatic switching device $r $nNSR641RF-D of Guodian Nanrui is suitable for backup power supply automatic switching devices of various voltage levels. The NSR641RF-DL can achieve segmented automatic switching and incoming line mutual switching, the NSR641RF-DT can achieve segmented automatic switching and transformer mutual switching, and the NSR641RF-DF can achieve segmented automatic switching, incoming segmented overcurrent protection, measurement and control, and operation functions.

Product Details

Guodian Nanrui NSR641RF-DT backup power automatic switching device

Function Configuration

The main functions of the protection of the backup power supply automatic switching device of Guodian Nanrui NSR641RF-DT include:1)Segmented self investment;2)Incoming line interconnection(NSR641RF-DLSpecial);3)Transformer interconnectionNSR641RF-DT(Special)4)Overload reduction;5)Segmented overvoltage protection for section I, overcurrent protection for section II, and post acceleration protection;6Segmented zero sequence overcurrent and acceleration after zero sequence overcurrent.

The main functions of measurement and control include:132 Road remote signal input acquisition, device remote signal displacementSOErecord;

Basic Logic of Self Investment

1 Voltage: Busbar voltage refers to the voltage between the two lines of the busbarUabTheUbcAt least one of them is greater than the rated voltage of the busbar; Incoming voltage fingerincoming linePTIf the phase voltage or line voltage is higher than the rated voltage of the incoming line (if there is no incoming line available on site)PT, can exit according to the control wordCriteria for incoming voltage).

2 No voltage: Busbar no voltage refers to the voltage of the two lines of the busbarUabTheUbcAll are less than the rated value of the busbar without voltage.

3 No current: No current in the incoming line refers to a phase current of the working power supply's incoming line connection device being less than the rated value of no current in the incoming line.

4 Backup automatic switching action and whole group reset: the working power supply meets the condition of no voltage and current, the backup power supply meets the condition of voltage, and the backup automatic switching entersWhen the entire group is reset, if the working power supply meets the condition of no current during the reset time, it will automatically switch on. Otherwise, when the entire group returnsBetween (fixed as)50s)After arrival, prepare for self discharge.

Segmented self investment

Segmented automatic switching is mainly used in single busbar segmented terminal substations, such as segmented backup automatic switching on the load side of the main transformer and bridge backup automatic switching on the power sidecast