German IFM sensor Yifumen PT5501+EVC04
PT5501IFM high-frequency dynamic pressure sensor, specifically designed for real-time monitoring of hydraulic/pneumatic systems.
EVC04Signal conversion module, which converts the raw signal of PT5501 into standard industrial signals (such as 4-20mA or 0-10V).
| parameter | Numerical/Characteristic | remark |
|---|---|---|
| measurement range | 0-600 Bar (optional range) | Typical industrial grade high voltage coverage |
| output signal | Original analog signal (mV level) | Need to cooperate with EVC04 conversion |
| precision | ±0.5% FS | Within the full range |
| response time | ≤1 ms | Suitable for dynamic pressure monitoring |
| medium temperature | -40°C ~ +125°C | Direct contact with oil/gas |
| Protection level | IP67 | oil-proof and water-resistant |
| electrical interface | M12 × 1 plug (5-pin) | Standard industrial connection |
Input compatibilityReceive the raw mV signal of PT5501.
output option:
4-20mA (two-wire system)
0-10V (three wire system)
RS-485 Modbus RTU (optional)
power supply voltage: 12-30V DC (wide voltage design).
Programmability: Through IFMCR0403Configure tools to adjust range/alarm thresholds.
hydraulic systemReal time monitoring of pump station pressure fluctuations.
pneumatic controlCylinder driven pressure feedback.
test benchHigh frequency pressure data acquisition (requires high-speed PLC).
PT5501:
Directly installed at the measuring point (G1/4 or M20 × 1.5 interface).
Avoid mechanical vibration interference with measurement accuracy.
EVC04:
DIN rail installation (standard 35mm rail).
Stay away from strong electromagnetic interference sources.
PT5501 → EVC04:
Pin1 (power+) → Pin1 (power+)
Pin2 (signal+) → Pin2 (signal input+)
Pin3 (shielding) → grounding terminal
EVC04 output example (4-20mA):
Pin+→ PLC AI module+
Pin - → PLC AI module-
| fault phenomenon | Possible reasons | solution |
|---|---|---|
| No output signal | Power supply abnormality/wiring error | Check the 24V power supply and polarity |
| Output value drift | Sensor overload/aging | Re calibrate or replace PT5501 |
| EVC04 communication failure | Configuration parameter error | Use CR0403 tool to restore factory settings |
| The reading is unstable | Media pulsation/mechanical vibration | Installing pulse dampers |
PT5502Higher range (1000 Bar)+digital output.
EVC05Upgrade module with HART protocol output.
| brand | Sensor+module | differentiating points |
|---|---|---|
| SICK | PT100 + AFM60A | Accuracy ± 0.3%, but response time 5ms |
| Bosch | SBP1120 + SCM100 | Only supports 4-20mA output |
| Parker | P7S + XSC-A | Integrated display, no need for additional modules |
CR0403 configurator:
Adjust the range and filtering parameters of EVC04.
Diagnostic Sensor Health Status (IFM)Service ToolSoftware).
calibration cycle:
It is recommended to calibrate once a year using IFMPK7520Calibration kit).
Standard kit:
PT5501 sensor (including G1/4 installation connector)+EVC04 module.
Optional accessories:
Explosion proof version (ATEX certification, suffix 'EX').
High temperature cable (-60 ° C~+200 ° C, code 'HT').
German IFM sensor Yifumen PT5501+EVC04