Technical Specifications
success cases
Related Products
Advantages and Features
The liquid level detection device designed can effectively avoid the influence of flotation foam, accurately measure the pulp liquid level height and foam layer thickness, and avoid the problem of being stuck and unable to measure;
Measurement range: 0~500mm, accuracy ± 2% of full range;
Each flotation cell is equipped with a touch screen for on-site operation, which facilitates intuitive and quick adjustments;
Data can be stored and curve queried;
The system adopts an open and standardized structure, with communication interfaces.
Flow chart of flotation liquid level/aeration control systemThe liquid level detection device detects the liquid level height or foam layer thickness in the flotation cell in real time, and transmits the signal to the PLC controller, which automatically adjusts the opening of the ore discharge valve according to the preset target value to ensure that the pulp level in the flotation cell is always kept within the optimal range.
The inflation control system is used to accurately control the supply of gas (usually air) in the flotation tank. The system adjusts the speed of the blower, the opening of the inlet valve, or other operating parameters of the inflation equipment to change the amount of gas injected into the slurry; The appropriate amount of inflation directly affects the dispersion of bubbles, the probability of contact between mineral particles and bubbles, and the flotation effect in the flotation process; Usually equipped with pressure sensors or flow meters, it monitors and adjusts the working status of the inflation equipment in real time.Technical Specifications
Measurement range:0~500mm;
Measurement accuracy:Better than ± 2% of the full range;
Control signal:4~20mA DC;
Electrical valve positioner input signal:4~20mA DC;
Laser rangefinder output signal:4~20mA DC;
Working environment temperature:-10℃~50℃;
Controller power supply:380VAC/220VAC instrument power supply 24VDC;