Welcome Customer !

Membership

Help

Xuchang Shangji Electric Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Xuchang Shangji Electric Co., Ltd

  • E-mail

    xjsjdq@163.com

  • Phone

    13069538188

  • Address

    Middle section of Xuji Avenue, Xuchang City, Henan Province

Contact Now

FCK-821A_Xuji Microcomputer Measurement and Control Device

NegotiableUpdate on 03/29
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The FCK-821A microcomputer measurement and control device is mainly developed as an interval layer measurement and control unit for substation automation systems with voltage levels ranging from 35kV to 110kV. It can also be used separately as a regular measurement and control device. This series of devices has functions such as measurement, control, monitoring, and recording, and supports the IEC 60870-5-104/IEC 61850 protocol.

Product Details

1. Overview

The FCK-821A microcomputer measurement and control device is mainly developed as an interval layer measurement and control unit for substation automation systems with voltage levels ranging from 35kV to 110kV. It can also be used separately as a regular measurement and control device. This series of devices has functions such as measurement, control, monitoring, and recording, and supports the IEC 60870-5-104/IEC 61850 protocol.


2. Main functional features


2.1 High precision measurement technology

32-bit high-performance DSP processor; 16 bit high-speed A/D; 32 point sampling;

Adopt software dynamic compensation technology for the transmission error of secondary TA;


2.2 High reliability software and hardware design

Adopting embedded RTOS;

Separate input and output, separate strong and weak electricity; Good electromagnetic compatibility.


2.3 Comprehensive self checking function

Self check of telemetry acquisition circuit;

Open circuit self-test (can detect the action coil of the outlet relay);

Self check of AD, FLASH, EEPROM chips.


2.4 Complete interval layer monitoring function

Monitoring: Humanized operating interface; Display the main wiring diagram of this interval;

Records: including remote signaling records, event records, alarm records, and operation records; Save a maximum of 100 entries in total;

Communication: The measurement and control device is directly connected to Ethernet and shares network channels with other intelligent devices for data sharing across the entire station.


2.5 Configurable

The number of telemetry points, signaling points, and remote control points can all be configured;

The main wiring diagram and gear monitoring function can be configured;

Specialized visual configuration tool;

Flexible configuration to meet the needs of various applications.


3. Main technical indicators


3.1 Communication measurement


3.1.1 Voltage

Input rated voltage: AC 57.7 V or 100 V, 50 Hz;

Accuracy: ± 0.2%;

Power consumption:<0.5 VA/phase.


3.1.2 Current

Rated input current: AC 5 A or 1 A, 50 Hz;

Accuracy: ± 0.2%;

Power consumption: less than 0.75 VA per phase at rated current of 5 A; Less than 0.5 VA per phase at rated current of 1A.


3.1.3 Frequency

Frequency range: 45 Hz to 55 Hz;

Accuracy: ± 0.02 Hz (software frequency measurement).


3.1.4 Power measurement

Active power P, reactive power Q, apparent power S, power factor.

The measurement accuracy is ± 0.5%.


3.2 DC measurement

Input range: Voltage source 0 V to+5 V;

Accuracy: ± 0.5% (when connected to an external temperature transmitter, temperature measurement error: ± 2 ℃).


3.3 Status Input

Input method: DC220V, DC110V or DC48V input, with photoelectric isolation;

Event sequence recording station resolution: ≤ 2 ms.


3.4 Electricity measurement

Pulse input method: DC 24V input, optoelectronic isolation;

Pulse width: ≥ 10 ms.

Integral electrical measurement with a measurement accuracy of ± 0.5%.


3.5 Control output contact capacity

DC: 30 V, 5 A;

Communication: 220 V, 5 A.


3.6 Working environment temperature

Work: -25 ℃ to+55 ℃;

Storage: -25 ℃ to+70 ℃.


3.7 Power Supply

AC:220 V, Allowable fluctuation range -10% to+10%;

DC: 110 V or 220 V, allowable fluctuation range -20% to+15%.


3.8 Electrical Insulation Performance

Insulation resistance: in accordance with the provisions of DL/T 630-1997;

Insulation strength: in accordance with the provisions of DL/T 630-1997;

Surge voltage resistance capability: in accordance with the provisions of DL/T 630-1997.


3.9 Mechanical Properties

Vibration: in accordance with the provisions of DL/T 630-1997;

Impact and collision: comply with the provisions of DL/T 630-1997.


3.10 Electromagnetic compatibility

Anti high frequency interference capability: able to withstand the high frequency interference test with severity level IV specified in 3.7.1 of GB/T 13729-2002;

Anti electrical fast transient interference capability: able to withstand the strict level IV fast transient interference test specified in GB/T 17626.4-1998;

Anti surge interference capability: able to withstand the severe level III surge interference test specified in GB/T 13729-2002;

Anti static discharge interference capability: able to withstand the strict level III static discharge interference test specified in 3.7.4 of GB/T 13729-2002;

Ability to resist power frequency magnetic field interference: able to withstand the power frequency magnetic field immunity test with severity level IV specified in 3.7.5 of GB/T 13729-2002;

Anti damping oscillation magnetic field interference capability: able to withstand the damping oscillation magnetic field anti-interference test with severity level IV specified in Chapter 5 of GB/T 17626.10-1998;

Anti radiation electromagnetic field disturbance capability: able to withstand the harsh level III radiation electromagnetic field disturbance test specified in Table 15 of GB/T 15153.1-1998.