FCK-801C microcomputer measurement and control device
Technical and user manual
Product Features
High precision measurement, ensuring a full range measurement accuracy of 0.2%.
The exit mode of "start+exit" and the start mode of dual command activation, as well as comprehensive software and hardware self checks, ensure the safe and reliable operation of the device.
The device adopts a fully enclosed chassis, with strict separation of strong and weak electricity, and strong anti-interference ability. Configure 3 Ethernet ports and support IEC61850 communication protocol.
The timing method supports SNTP timing, B-code timing, and GPS pulse timing. Complete report records, capable of storing 80 event records, 80 operation records, 80 remote signaling records, and 80 alarm records. Adopting a 320 * 240 large screen LCD display, a friendly human-machine interface, and a fully Chinese Windows menu mode, the structure is clear and easy to use. The function configuration is complete and can be selected through configuration tools to meet the personalized needs of customers. Xuji's independently owned "VLD" visualization tool has high software reliability.
2.1.1 Collection Capacity
Up to 12 channels, available in four models: 3I4U, 4I8U, 6I6U, and 12U; DC: Up to 3 channels, optional with 3 DC inputs or without DC inputs.
2.1.2 Input rated voltage: 100/3 V, 100 V; Current: 5 A or 1 A.
2.1.3 Measurement range: Voltage and current: 0-120% of rated value; DC: 0-5 V or 4-20 mA; frequency: 42-60 Hz.
2.1.4 Measurement accuracy Voltage and current: ± 0.2%; Active power, reactive power, apparent power, power factor, DC: ± 0.5%; Frequency: ± 0.01 Hz.
2.1.5 Power consumption
AC current circuit: when the rated current is 1 A, each phase shall not exceed 0.5 VA; when the rated current is 5 A, each phase shall not exceed 0.75 VA; AC voltage circuit: each phase shall not exceed 0.5 VA;
DC circuit: 220V input, power consumption of each input circuit is within the range of 0.2 W to 0.6 W, 110V input, power consumption of each input circuit is within the range of 0.1 W to 0.4 W.
2.1.6 Harmonic measurement 13th harmonic measurement.
2.2.1 The maximum collection capacity is 64 remote signaling inputs.
2.2.2 Input method: DC220 V or DC110 V input, with photoelectric isolation;
Event sequence recording resolution: ≤ 1ms.
The maximum output capacity is 24 remote control output contacts.
The contact method is normally open passive air contact.
Contact capacity AC: 220 V, 5 A; DC: 30V, 5A.
Working power supply AC: 220V, allowable fluctuation range -20% to+15%, frequency 50HZ (allowable deviation ± 1 Hz), sine wave (distortion coefficient not exceeding 5%); DC: 110 V or 220 V, allowable fluctuation range -20% to+15%, ripple coefficient not exceeding 5%