Welcome Customer !

Membership

Help

Shanghai Shengxu Electric Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products

Shanghai Shengxu Electric Co., Ltd

  • E-mail

  • Phone

  • Address

    Jiangyang South Road, Zhabei District, Shanghai

Contact Now

ES3010E soil resistivity tester

NegotiableUpdate on 05/06
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The ES3010E soil resistivity tester can accurately detect grounding resistance, soil resistivity, and grounding voltage. It uses fast filtering technology to reduce interference to a minimum of Z. Simultaneously store 500 sets of data.

Product Details

1、 Overview:

ES3010E soil resistivity testerThe grounding resistance soil resistivity tester, also known as the four wire grounding resistance tester or soil resistivity tester, is a commonly used instrument for testing and measuring grounding resistance. It adopts a large LCD gray white screen backlight display and microprocessor technology, and is controlled by a microprocessor for 2-wire, 3-wire, and 4-wire grounding resistance testing and soil resistivity testing.

ES3010E soil resistivity testerIt gathers many grounding testing functions, which can quickly and comprehensively measure various parameters in the grounding network. It is a new generation of grounding measuring instrument that replaces traditional shaking table measurement. Widely used in telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, iron tower transmission lines, gas stations, factory grounding grids, lightning rods, etc. Instruments have the characteristics of precise, fast, simple, stable and reliable testing.

2、 Technical specifications:

1. Range and accuracy errors

measurement function

measurement range

precision

resolution

Grounding resistance (R)

0.00Ω to 30.00Ω

±2%rdg±5dgt (注1)

0.01Ω

30.0Ω to 300.0Ω

±2%rdg±3dgt

0.1Ω

300Ω to 3000Ω

±2%rdg±3dgt

3.00kΩ~30.00kΩ

±2%rdg±3dgt

10Ω

Soil resistivity (ρ)

0.00Ωm~99.99Ωm

ρ=2 π aR (Note 2)

0.01Ωm

100.0Ωm~999.9Ωm

0.1Ωm

1000Ωm~9999Ωm

1Ωm

10.00kΩm~99.99kΩm

10Ωm

100.0kΩm~999.9kΩm

100Ωm

1000kΩm~9999kΩm

1kΩm

ground voltage

AC 0.00~600V

±2%rdg±3dgt

0.01V

Note: 1 Reference condition: Accuracy when Rh Rs<100 Ω.

Working conditions: Rh max=3k Ω+100R < 50k Ω; Rs max=3k Ω+100R < 50k Ω

2. It depends on the measurement accuracy of R, π=3.14, a: 1m~100m;

Controlled by a microprocessor, it can accurately detect grounding resistance, soil resistivity, and grounding voltage. It uses fast filtering technology to minimize interference. Simultaneously store 500 sets of data.

2. General specifications

Function

Measure grounding resistance and soil resistivity using two, three, and four wires;

Ground voltage measurement

Environmental temperature and humidity

23 ℃± 5 ℃, below 75% RH

Power supply

6 1.5V (LR14) alkaline batteries

Interference voltage

<20V (should be avoided)

Interference current

<2A (should be avoided)

Electrode spacing during R measurement

a>5d

Electrode spacing when measuring ρ

a>20h

Auxiliary grounding resistance value

Reference condition<100 Ω, working condition<5k Ω

Range

Grounding resistance: 0.00 Ω~30.00k Ω

Soil resistivity: 0.00 Ω m~9999k Ω m

Grounding voltage: 0.00V~600V

measurement method

Precision 4-wire, 3-wire method measurement, simple 2-wire measurement of grounding resistance

measurement method

Grounding resistance: rated current pole changing method

Soil resistivity: Quadrupole method

Grounding voltage: average rectification (between S-ES interfaces)

test frequency

128Hz

Short circuit test current

AC>20mA (sine wave)

Open circuit test voltage

AC 28V max

Test voltage waveform

sine wave

Range of electrode spacing

Can be set from 1m to 100m

Shift gears

Grounding resistance: 0.00 Ω~30.00k Ω Fully automatic shifting

Soil resistivity: 0.00 Ω m~9999k Ω m Fully automatic shifting

Backlight

Controllable gray white backlight, suitable for use in dark fields

display mode

4-digit ultra large LCD display with gray white backlight

Measurement indication

LED flashing during measurement

LCD display domain

108mm×65mm

Instrument size

240mm (length) × 188mm (width) × 85mm (height)

Standard testing line

4 pieces: Red 15m, Black 15m, Yellow 10m, Green 10m each

Simple testing line

2 pieces: 1 yellow 1.5m, 1 green 1.5m each

Auxiliary grounding rod

4 pieces

measure time

Ground voltage: about 2 times/second

Grounding resistance and soil resistivity: about 7 seconds/time

ground voltage

Measurement below AC 600V (grounding voltage measurement function cannot be used to measure commercial electricity)

data storage

500 sets, "MEM" storage indicator, displaying the "FULL" symbol to indicate that the storage is full

data lookup

When consulting data, the "MR" symbol indicates

Overflow display

The "OL" symbol indicates overflow of over range

alarm function

When the measured value exceeds the alarm set value, an alarm prompt will be issued

battery voltage

Insufficient battery voltage, displaying low battery symbol ""

Auto Shutdown

APO "indicates that it will automatically shut down after 15 minutes of startup

Power consumption

Standby: 40mA Max (backlight off)

Power on backlight: 43mA Max

Measurement: 120mA Max (backlight off)

Quality

Instrument: 1280g (including battery)

Test line: 890g (including simple test line)

Auxiliary grounding rod: 720g (4 pieces)

Working temperature and humidity

-10℃~40℃; Below 80% RH

Storage temperature and humidity

-20℃~60℃; Below 70% RH

overload protection

Measure grounding resistance: AC 280V/3 seconds between ports H-E and S-ES

insulation resistance

20M Ω or above (500V between circuit and casing)

Voltage resistance

AC 3700V/rms (between circuit and casing)

electromagnetic properties

IEC61326(EMC)

Suitable for safety regulations

IEC61010-1 (CAT III 300V, CAT IV 150V, pollution level 2);

IEC61010-031;

IEC61557-1 (Grounding Resistance);

IEC61557-5 (soil resistivity);

JJG 366-2004。 Product Quality Commitment:

1. The manufacturing and testing of the product comply with national standards.

2. The product is tested by professional inspectors to ensure that all indicators meet your requirements.

3. If there are any quality issues with the products we provide during the warranty period, we are willing to take full responsibility.