EOCRi3MZ-WRCUW Schneider Communication Motor Protector

NegotiableUpdate on 05/19
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

EOCRi3MZ-WRCUW Schneider Communication Motor Protector Shanghai Hanshi Electric EOCR-i3MZ: 32-bit MCU for precise protection, #177; 1% precision measurement, integrated with 12 protection functions including overload, underload, and phase loss, supports Modbus remote communication, UL/CCC certification, and provides intelligent protection for industrial equipment

Product Details

EOCRi3MZ-WRCUW Schneider Communication Motor Protector

Shanghai Hanshi Electric Co., Ltd. specializes in agency salesEOCR-i3MZIntelligent motor protector,,EOCR-I3MZThe motor protector has overcurrent, undercurrent, reverse rotation, phase loss, stall, current imbalance, and leakage protection functions, and hasModbus RS-485Communication function, which can read the three-phase current value and leakage current value in real time through communication, and record the fault type and the cause of the last three faults.


Product features

built-inMCU(microprocessor control unit)

real-time monitoring/high precision

Protection functions: overcurrent, undercurrent, reverse, phase loss, stall, current imbalance,grounding

Additional functions: power failure protection, accumulated running time, recording the causes and currents of three faults after failure, and multiple reset mode options

Enhanced monitoring function: cyclic display of three-phase current and grounding current&Reason display for tripping

time limit/inverse time/Overheating inverse time limit can be selected

The current amplitude bar can display the real-time operation status of the load

Communication method:Modbus RS-485

For split type products, even if not connectedPDMRecognize the provision of normal protection functions

EOCRi3MZ-WRCUW Schneider Communication Motor Protector

Overview of EOCR-i3MZ

32-bit MCU+True RMS measurement, accuracy ± 1%

Protection functions: overload (OC), underload (UC), phase loss (PL), reverse phase (RP), imbalance (Ub), startup stall (Sc), running stall (JA), leakage (lg)

High frequency component filtering - the function of measuring and removing high-frequency components and pulse noise components of leakage current

Action time characteristics: timed limit, inverse time limit, thermal accumulation inverse time limit

THD total harmonic distortion monitoring: real-time monitoring of three-phase, adjustable alarm threshold

Modbus RTU/RS-485 2400-38 400 bps remote communication

Display: Bar load graph+5-digit seven segment digital tube LED

Three phase current automatic rotation display/manual locking of a certain phase display (manual locking function)

Operation/Fault Records:

• Reasons for tripping and current records of the last 3 faults

Accumulated running time and timeout alarm records

• Limit the number of startup records

Fail Safe mode: independent start stop function (safe mode)

Password protection function: Three digit password to prevent accidental operation; Long term shutdown can restore factory settings

Reset mode: manual, automatic, power-off, remote communication

Structural selection: Terminal T, Bottom hole H, Window W

Three phase/single-phase modeMenu switchable

Compliance and certification: UL, CCC, compliant with EU RoHS



EOCRI3MZ/IFMZ wiring diagram

EOCRi3MZ-WRCUW施耐德通讯马达保护器

EOCR-I3MZ/IFMZ Dimensional Drawing

EOCRi3MZ-WRCUW施耐德通讯马达保护器

protection function

protection function

Protection action time

overcurrent

0.2~30Seconds (timed limit),1-30class(Inverse time limit)

undercurrent

OFF,1~10Adjustable in seconds

phase loss

OFF,0.5~5Adjustable in seconds

locked-rotor

0.3~5Adjustable in seconds

stall

D-Time

Reverse phase (reversal)

0.15within seconds

current imbalance

1~10Adjustable in seconds