The transformer winding deformation tester quantifies the response changes of the internal winding parameters of the transformer in different frequency domains, and determines the degree of change in the internal winding of the transformer based on the magnitude of the change, the amplitude and region of the frequency response change, and the trend of the frequency response change. Therefore, the measurement results can be used to determine whether the transformer has been severely damaged and whether major repairs are needed.
Features
By using DDS dedicated digital high-speed scanning technology, it is possible to accurately diagnose winding distortion, bulging, displacement, tilting, inter turn short circuit deformation, and phase to phase changes
Contact short circuit and other faults.
The signal output amplitude can be adjusted by software, with a maximum peak amplitude of ± 10V.
It has dual measurement system functions of linear sweep frequency measurement and segmented sweep frequency measurement, and is compatible with the measurement modes of two current domestic technology schools.
Automatic data analysis system for detecting and comparing winding similarity between phases A, B, and C horizontally.
Technical Specifications
| scanning method | Linear scanning frequency measurement range: (1kHz)~(2MHz), 2000 scanning points, resolution of 1kHz |
| Segmented sweep frequency measurement sweep frequency measurement range: (0.5kHz)~(1MHz), 2000 sweep frequency points | |
| Other technical parameters | Range of amplitude measurement: (-100dB) to (+20dB) |
| Amplitude measurement accuracy: 0.1dB | |
| Scanning frequency accuracy: 0.01% | |
| Signal input impedance: 1M Ω | |
| Signal output impedance: 50 Ω | |
| Same phase test repetition rate: 99.5% |