Comprehensive testing instrument for the characteristics of full function transformers (Hangzhou, Yangzhou)

NegotiableUpdate on 01/20
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The fully functional transformer characteristic comprehensive tester is used for automatic testing of protective and metering CT/PT, suitable for laboratory and on-site testing. If it is not in a laboratory environment, the tester must be reliably grounded before it can be used. The selection of grounding point should be as close as possible to the test object, and during testing, always keep one terminal on the high-voltage side of the transformer grounded.

Product Details

Other name

Fully automatic transformer characteristic comprehensive tester, transformer comprehensive characteristic tester, volt ampere characteristic transformation ratio polarity comprehensive testerCT volt ampere characteristic comprehensive tester, transformer multifunctional tester

Product Overview

Comprehensive tester for the characteristics of full function transformersUsed for protection and measurement purposesCT/PT performs automatic testing, suitable for both laboratory and on-site testing. If it is not in a laboratory environment, the tester must be reliably grounded before it can be used. The selection of grounding point should be as close as possible to the test objectDuring testing, always keep one terminal on the high-voltage side of the transformer grounded.When measuring the transformation ratio of a transformer, please ensure that the wiring is correct, otherwise life-threatening voltage may be generated inside the transformer and the connected transformer may be damaged by the tester.

Comprehensive tester for the characteristics of full function transformersFeatures

• Support detection of CT and PT

Meet the requirements of regulations such as GB1207 and GB1208

Without the need for external auxiliary equipment, all testing items can be completed on a single machine

Equipped with a miniature fast printer, it can directly print test results on site

Easy to operate with intelligent prompts, making it easier for users to get started. .

Large screen LCD with graphical display interface

Automatically provide CT/PT (excitation) inflection point values according to regulations

Automatically provide 5% and 10% error curves

Can save 3000 sets of test data without losing it after power failure

Supports USB flash drive data transfer, which can be read through a standard PC and generate WORD reports

Small and lightweight ≤ 22Kg, very conducive to on-site testing

CT (protective, metrological)

PT

Voltage current characteristic (excitation characteristic) curve

Voltage current characteristic (excitation characteristic) curve

• Automatically provide inflection point values

• Automatically provide inflection point values

Automatically provide error curves of 5% and 10%

• Ratio measurement

• Ratio measurement

• Polarity judgment

• Differential measurement

• Differential measurement

• Phase (angle difference) measurement

• Phase (angle difference) measurement

• Polarity judgment

• Communication voltage withstand test

• One flow test

• Secondary load test

• Communication voltage withstand test

• Secondary winding test

• Secondary load test

• Iron core demagnetization

• Secondary winding test

• Iron core demagnetization

technical indicators

item eye

ginseng number

working power supply

AC220V±10% 、50Hz

Device output

0-2500Vrms, 5Arms (20A peak)

Note:0-5A is the true value, and values greater than 5A-20A are the calculated values

High current output

0~1000A

Excitation accuracy

≤ 0.5% (0.2% * reading+0.3% * range)

Secondary winding

resistance measurement

scope

0.1~300Ω

precision

≤ 0.5% (0.2% * reading+0.3% * range)

Secondary actual

Load measurement

scope

5~500VA

precision

≤ 0.5% (0.2% * reading+0.3% * range) ± 0.1VA

phase measurement

(Angle difference)

precision

4min

resolution

0.1min

worse than

precision

0.05%

CT

Variable ratio measurement

scope

≤25000A/5A(5000A/1A)

precision

≤0.5%

PT

Variable ratio measurement

scope

≤500KV

precision

≤0.5%

working environment

Temperature: -10 ℃~40 ℃, humidity: ≤ 90%, altitude: ≤ 1000m

Size and weight

Size:410mm × 260mm × 340mm, weight: ≤ 22Kg