- Phone
-
Address
Jiangyang South Road, Zhabei District, Shanghai
Shanghai Shengxu Electric Co., Ltd
Jiangyang South Road, Zhabei District, Shanghai
Product Introduction
The DC resistance of transformers is a necessary measurement item for semi-finished and finished products in transformer manufacturing, factory testing, installation, handover testing, and preventive testing by the power department,BZC-3S Three Circuit Transformer DC Resistance TesterIt can effectively detect manufacturing defects such as material selection, welding, loose connection parts, missing strands, and broken wires of transformer coils, as well as hidden dangers that exist after operation.
Product features
1. When testing windings with neutral point leads in the star connection method, the instrument can adopt a three-phase simultaneous measurement method to test the DC resistance of A0, B0, and C0 phases, greatly saving testing time;
2. Display and print all test data of the high, medium, and low voltage windings of the transformer, and automatically calculate the three-phase unbalance rate;
3BZC-3S Three Circuit Transformer DC Resistance TesterEquipped with reverse electromotive force protection function;
4. Equipped with automatic discharge and discharge indication functions, reducing misoperation and ensuring equipment and personnel safety;
5. The instrument can store 500 sets of test data and can also use a USB drive to store data;
6. The instrument adopts a 5.7-inch ultra large LCD display, which can print test results at any time;
7. The instrument has the characteristics of wide temperature range, high accuracy, shock resistance, anti-interference, and easy portability.
parameter
Output current: Three phase test: 2 * 10A, 2 * 5A, 2 * 2A
Single phase testing: 20A, 10A, 2A
Test range: 2 * 10A: 500 μ Ω~ 500m Ω
2*5A: 1mΩ~1Ω
2*2A: 2.5mΩ~2.5Ω
20A: 250 um
10A: 500 um
2A: 2.5mΩ~10Ω
Resolution 0.1 μ Ω
Measurement accuracy ± (0.2% reading+2 words)
Dimensions 420mm × 250mm × 340mm
Environmental temperature -10 ℃~50 ℃
Environmental humidity ≤ 85% RH
Working power supply AC220V ± 10%
Power frequency 50 ± 1Hz
Instrument weight 15kg