Air cooled heat pump unit

NegotiableUpdate on 04/08
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

1. The high-efficiency energy-saving unit can be equipped with an independently patented heat recovery device. The heat recovery does not consume energy, and the overall efficiency of the unit can be increased by 5%, with an energy efficiency of up to 6.02. The unit has a single and double circuit design for reliable operation, meeting customer needs. Before leaving the factory, the unit undergoes safety testing to ensure that its performance meets enterprise standards. The intelligent control adopts microcomputer control, which can centrally manage system operations. Optional remote management program feedback system operation information to achieve remote service

Product Details

Product details configuration

Screw compressor+frequency conversion technology
Selecting Hanzhong brand semi enclosed twin-screw compressor, the compressor adopts cast iron shell, forged steel rotor, SKF bearings, which are efficient, energy-saving, durable, and have a long service life
By adopting onboard variable frequency drive technology and selecting Danfoss brand variable frequency drives, the energy efficiency of the chiller unit has been significantly improved under partial load conditions. The comprehensive partial load performance (IPLV) can reach around 10.0, and the energy-saving effect is significant
变频装置
shell and-tube evaporator
The evaporator adopts a full liquid or falling film design, with refrigerant flowing through the shell side and water flowing through the tube side. The copper tube adopts 1.1mm thick copper heat exchange tube, ensuring that all products meet the high requirements of high efficiency, energy saving, safety, strong anti pollution ability, and durability
蒸发器
finned cooler
The fins are made of hydrophilic corrugated aluminum sheets, with a reasonable arrangement of copper pipes and a 'V' - shaped installation to improve heat transfer efficiency and reduce fan noise. Copper pipes and aluminum fins are tightly mechanically expanded, resulting in high performance and stable heat transfer. Adopting an external rotor axial flow fan, it has low noise, high airflow, high efficiency, and sufficient dynamic pressure
翅片冷凝器
Heat recovery device
The condensation heat of the chiller unit (usually discharged into the atmosphere through the cooling tower) is recovered and effectively utilized. With the heat recovery cycle, the heat absorbed during refrigeration can be transported to the areas of the building that require hot water through heat recovery. During the cooling season, hot water above 50 ℃ can be provided for free
热回收冷水机组
Human machine interface and control center
Adopting advanced and highly integrated PLC integrated controller, fully automatic operation, can be connected to Modbs upper computer system, 10 inch full-color human-machine interaction interface, simple operation, equipment operation data, fault display and solutions are clear at a glance, and can be connected to operation service system
显示屏
IoT cloud service platform (remote control)
Equipped with advanced IoT cloud service platform, remote control can be achieved through mobile APP, real-time display of unit operation data, providing SMS pre alarm function, completely eliminating the need for on-site personnel duty, greatly reducing personnel costs
云平台

Customer Case

国家同步辐射实验室

National Synchrotron Radiation Laboratory

杭州清正生物科技股份有限公司

Hangzhou Qingzheng Biotechnology Co., Ltd

铜陵鑫克精细化工有限责任公司

Tongling Xinke Fine Chemical Co., Ltd

More cases

Advantages of Stellar Seasons

恒星世季优势

20 Technology Sedimentation Casting Fine Star Seasons

20 years of production and manufacturing experience, 3 major production bases, 50000 square meters of production plants, fully automated production lines, national calibration and testing system, 108 production processes with strict quality control management to ensure that the quality of each product meets national quality standards

40 patented technologies save 30% energy

Jointly established a refrigeration system project design and research institute with the University of Science and Technology of China, with 4000 industry solution experiences, over 40 patented technologies, and energy savings of over 30% in operation

恒星世季优势
恒星世季优势

Professional technical team provides free solution design

A technical team of 20 people provides free targeted overall solutions for different enterprise project situations. According to enterprise needs, customized and reliable systems can be provided to safeguard enterprise production

Double after-sales service guarantee solves worries

7 × 24-hour after-sales service team, IoT mobile APP remote monitoring system, providing fault warning function to reduce the impact of equipment failure, lifetime warranty, and helping enterprise development

恒星世季优势
-

Technical parameters of air-cooled screw heat pump unit
type number 40STE-Model 110AHS4 160AHS4 210AHS4
110AHSB4 160AHSB4 210AHSB4
refrigerant Refrigerant R22 R407C R134a R22 R407C R134a R22 R407C R134a
Nominal Refrigerating Capacity
Rated cooling capacity
×1000 kcAHl/h 102.7 95.2 66.9 146.1 138.6 99.0 196.0 184.7 131.0
kW 119 111 78 170 161 115 228 215 152
USRT 34.0 31.5 22.1 48.3 45.8 32.7 64.8 61.1 43.3
Compressor input power kW × 1 34.7 34.6 23.2 47.7 48.2 32.8 63.2 63.8 43.4
Nominal heating capacity
Rated heating capacity
×1000 kcAHl/h 112.2 104.6 70.1 157.4 149.9 102.1 211.1 199.8 135.1
kW 130 122 82 183 174 119 246 232 157
USRT 37.1 34.6 23.2 52 49.6 33.8 69.8 66.1 44.7
Compressor input power kW × 1 32.6 34.1 22 44.8 47.4 31 59.6 62.8 40.9
electricity source Power supply 3φ-380V-50Hz
protective device Protection device Reverse phase protection, phase loss protection, overcurrent protection, exhaust temperature protection, high and low voltage protection, low temperature protection, reserved water flow protection interface

Phase Peversion Protection、Phase Lack Protection、Overload Current Protection、The Reserved Water Protection Interface

制冷回路 Number of refrigeration circuits 1
Energy control% Capacity control 0,66,100 0,50,75,100
Refrigerant Charge Refrigerant Charge(kg) 33 45 51
Air side heat exchangerAir Coled Heat Exchanger Copper tube with corrugated aluminum fins
Water side heat exchanger
Water Side Heat Exchanger

inlet and outlet pipe diameter
Dia. Of Pipe(inch)
2-1/2' 3' 3'
Maximum pressure on the water side (MPa)
1
Frozen water flow rate
Chilled Water Folw (L/m)
20.5 19 13.4 29.2 27.7 19.8 39.2 36.9 26.2
Water pressure drop
Water Pressure drop(Kpa)
28 28 28 33 33 33 48 48 48
axial flow fan
Axial Fan
air flow×1000m³/h 56.8 56.8 56.8 80.4 80.4 56.8 85.2 85.2 80.4
powerNumber of units 1.2×4 1.2×4 1.2×4 2.0×4 2.0×4 1.2×4 1.2×6 1.2×6 2.0×4
Running noise Running noise dB(AH) 68 68 68
Total weight Total Weight(kg) 1550 1960 2940
Runnig weight (kg) 1660 2140 3160
Heat recovery technical parameters Reclaimed Data
Refrigerant Charge Refrigerant Charge(kg) 35 47 54
Heat recovery capacity
Heaet Reciaimed Volume
×1000 kcAHl/h 30.8 28.6 20.1 43.8 41.6 29.7 58.8 55.4 39.3
kW 36 33 23 51 48 35 68 64 46
USRT 10.2 9.4 6.6 14.5 13.7 9.8 19.4 18.3 13.0
Heat recovery device
Heat Recoverer
Import and export pipe diameter Dia. Ov Pipe(inch) 1-1/2″ 1-1/2″ 1-1/2″
Maximum pressure on the water side
Water Side Max Pressure (Mpa)
1
Sanitary hot water flow rate
Reclaimed Water Flow(m3/h)
6.2 5.7 4.0 8.8 8.3 5.9 11.8 11.1 7.9
Water pressure drop Pressure drop(Kpa) 24 24 24 23 23 23 27 27 27
Total weight Total Weight(kg) 1720 2160 3180
operating weight Runnig weight(kg) 1870 2400 3450

-

Note:
1. Nominal cooling capacity benchmark: air dry/wet bulb temperature: 35 ℃/24 ℃, frozen water inlet and outlet temperature: 12 ℃/7 ℃;
Dirt coefficient 0.088 ㎡·℃/kW
2. Nominal heating standard: air dry/wet bulb temperature: 7 ℃/6 ℃, hot water inlet and outlet temperature: 40 ℃/45 ℃;
3. Inlet and outlet water temperature during heat recovery period: 50 ℃/55 ℃;
4. Temperature range of frozen water: 5 ℃ -20 ℃;
5. Hot water temperature range: 45 ℃ -50 ℃;
6. Environmental temperature range: -5 ℃ -43 ℃;
7. The specifications and external dimensions may change without prior notice due to product improvements.