ATyS A and ATyS C are 4-pole automatic transfer switches with clear disconnect indication.
They include functions designed for mains/mains and mains/generator applications.
In automatic mode, they can monitor two power supplies based on parameters configured through DIP switches and switch between the two power supplies
Load conversion.
This product is designed for low-voltage power supply systems that can accept brief interruptions in load power supply during transmission.
ATyS C can be remotely monitored through RS485 communication.
advantage
Quick debugging
The tap voltage and wiring harness are included in a single package for the electric transfer switch and ATS controller. ATyS A and C switches can be used
Save a lot of time during the debugging process (which takes 2 to 3 minutes). Thanks to allowing access through eight DIP switches
The debugging design only requires the use of a screwdriver to configure the controller.
ATyS C using RS485 communication
RS485 communication enables remote monitoring of available power sources, their parameters, and timers. The communication speed is as high as 38400 baud.
split-type design
The split design of the transfer switch makes the installation of the ATS controller door easy and straightforward. While providing IP4x protection level, it also allows access to visual information on power availability and switch positions, as well as manual remote control options.
Watchdog relay used to check product availability
The ATyS A and ATyS C products are equipped with watchdog relays for continuous monitoring of your products, ensuring equipment safety. This relay can inform users in real time about the availability of the product, that is, whether the product is operating normally and ready for power switching.
harness
The wiring harness is a convenient method for supplying power to the ATyS A or ATyS C switch system. It is equipped with a voltage tap changer that provides a reliable link between the controller and the transfer switch to achieve:
-Track power availability
-Monitor the availability of the conversion switch
-Electrical interlock function
-Control and rotation between power sources
The length of the wiring harness is about 2 meters.
一般特性
• Mains/mains and mains/generator power grids.
ATS: I-0-II with 3 stable positions.
• Built in mechanical interlocking mechanism.
Emergency manual operation handle.
• Top or bottom input power supply.
ATS controller detects self power supply: 184-300 VAC.
The ATS controller can choose a 24 VDC auxiliary power supply.
Three phase+neutral line or single-phase+neutral line power grid.
• Voltage detection on all phases.
• Phase sequence check.
RS485 Modbus communication with ATyS C
Install controllers on doors or DIN rails.