E-mail
Shbsdq@163.com
- Phone
-
Address
South Industrial Park, No. 8 Huaijiang Avenue, Baoying, Yangzhou City, Jiangsu Province
Baoying Jindi Power Equipment Co., Ltd
Shbsdq@163.com
South Industrial Park, No. 8 Huaijiang Avenue, Baoying, Yangzhou City, Jiangsu Province

1、 Function Description
The AC power frequency withstand voltage test equipment meets the requirements of the national standard DL/T848.2-2004 for test transformers. The product has the characteristics of small size, light weight, compact structure, complete functions, and easy use. It is a high-voltage testing instrument used in power, industrial and mining, scientific research and other departments to conduct power frequency withstand voltage tests and DC leakage tests on various high-voltage electrical equipment, electrical components, and insulation materials.
The AC power frequency withstand voltage test equipment adopts a same core cylindrical multi-layer tower structure, with the primary low-voltage winding wound on the iron core and the secondary high-voltage winding wound on the outside of the low-voltage winding. This coaxial arrangement reduces coupling losses between windings. The high-voltage silicon stack is packaged in a sleeve using a process, and the outer shell of the product is made into an octagonal structure that matches the core. The overall appearance is beautiful and elegant
1、 Technical indicators
1. Environmental conditions for use
The ambient temperature shall not be higher than+40 ℃ and not lower than -20 ℃;
The relative humidity of the air is not greater than 90%;
Altitude not exceeding 3500 meters;
2. Working voltage
The input voltage of the power control box (unit) is AC 220V or 380V, and the relative error does not exceed ± 10%; (The specific voltage to be used is selected according to the specifications of the test transformer specified by the user)
Specifications |
capacity (kva) |
high voltage output |
Low voltage input |
instrument |
transformation ratio |
Temperature rise ℃ |
||
|
|
Voltage (kV) |
Current (mA) |
Voltage (V) |
Current (A) |
Voltage (V) |
High/Instrument |
30 minutes |
1.5/50 |
1.5 |
50 |
30 |
200 |
7.5 |
100 |
500 |
10 |
3/50 |
3 |
50 |
60 |
200 |
15 |
100 |
500 |
10 |
3/60 |
3 |
60 |
50 |
200 |
15 |
100 |
600 |
10 |
5/50 |
5 |
50 |
100 |
200 |
25 |
100 |
500 |
10 |
10/50 |
10 |
50 |
200 |
200 |
50 |
100 |
500 |
10 |
20/50 |
20 |
50 |
400 |
380 |
53 |
100 |
500 |
10 |
30/50 |
30 |
50 |
600 |
380 |
79 |
100 |
500 |
10 |
50/50 |
50 |
50 |
1000 |
380 |
120 |
100 |
500 |
10 |
5/100 |
5 |
100 |
50 |
380 |
13 |
100 |
1000 |
10 |
10/100 |
10 |
100 |
100 |
380 |
26 |
100 |
1000 |
10 |
20/100 |
20 |
100 |
200 |
380 |
53 |
100 |
1000 |
10 |
30/100 |
30 |
100 |
300 |
380 |
79 |
100 |
1000 |
10 |
50/100 |
50 |
100 |
500 |
380 |
132 |
100 |
1000 |
10 |
100/100 |
100 |
100 |
1000 |
380 |
263 |
100 |
1000 |
10 |
20/150 |
20 |
150 |
130 |
380 |
53 |
150 |
1000 |
10 |
30/150 |
30 |
150 |
200 |
380 |
79 |
150 |
1000 |
10 |
50/150 |
50 |
150 |
330 |
380 |
132 |
150 |
1000 |
10 |
100/150 |
100 |
150 |
665 |
380 |
263 |
150 |
1000 |
10 |