Technical Parameter
input
sensor type
303A/B1: Pt100,Pt1000,Cu50,Cu100
303A/B2: S,R,B,K,N,E,J,T,WRe3-25
303A/B3: Pt100,Pt1000,Cu50,Cu100,S,R,B,K,N,E,J,T,WRe3-25
Accept user specifications
Connection method
303A/B1: A two, three, or four wire heating resistance sensor
303A/B2: One thermocouple sensor and one thermistor sensor (three wire) are used for cold junction compensation, or a fixed cold junction temperature can be set for compensation without a thermistor sensor. The built-in thermistor sensor of the transmitter can also be used for cold junction compensation (the compensation accuracy will affect the final measurement accuracy)
303A/B3: Adopt 303A/B1 or 303A/B2 connection method according to requirements
measuring range
See Appendix 1: List of Input Sensor Types and Accuracy
response time
≤ 250ms with sensor for short circuit and open circuit monitoring
measurement accuracy
Digital measurement accuracy
See Appendix 1: List of Input Sensor Types and Accuracy
Long-term Drift
First year<0.035% full scale
Temperature influence
See Appendix 2: Effects of Environmental Temperature
rated operation conditions
ambient temperature
-40~85℃ -20~60 ℃ (explosion-proof type)
condensation
allow
electromagnetic compatibility
GB/T 17626, three-level
Protection level according to EN 60529
IP67
design
casing
Aluminum die-casting parts
weight
1.3kg (excluding temperature sensor)
Cable sealing pipe connection thread
M20 × 1.5 Other threads require adapter
Sensor connection
Integrated
split type
size
See Appendix 3: Dimensional Drawing of Two Wire Intelligent Temperature Transmitter
Display and Control
Display Size
33×23mm
Display digits
5 people
Unit (switchable)
℃ or ℉
set an option
Three buttons on the panel or PC
power supply
+24V DC ±5%
Certificates and approvals
Explosion proof type
ExdⅡCT6
Intrinsically safe type
ExiaⅡCT6
communication interface
RS485 Modbus RTU
Transmitter factory settings
sensor
Pt100 or B-type thermocouple or as specified by the customer
sensor offset
0℃
damping
0.0S