Technical Parameter
input
sensor type
301A/B1: Pt100,Pt1000,Cu50,Cu100
301A/B2: S,R,B,K,N,E,J,T,WRe3-25
301A/B3: Pt100,Pt1000,Cu50,Cu100
S,R,B,K,N,E,J,T,WRe3-25
Accept user specifications
Connection method
301A/B1: A two, three, or four wire heating resistance sensor
301A/B2: One thermocouple sensor and one thermistor sensor (three wire) are used for cold junction compensation, or a fixed cold junction temperature can be set for compensation without a thermistor sensor. The built-in thermistor sensor of the transmitter can also be used for cold junction compensation (the compensation accuracy will affect the final measurement accuracy)
301A/B3: Adopt the connection method of 301A/B1 or 301A/B2 according to the requirements
response time
≤ 250ms with sensor for short circuit and open circuit monitoring
output
Two wire system 4-20mA
HART
Load resistance Ra
Ra ≤ (Us-14.7V)/0.024A, Us is the loop voltage
sensor fault
Short circuit: Accept user specified (3.5~3.75mA)
Open circuit: Accept user specified (21)~23mA)
system failure
Can be set to 3.2mA or 24mA
measurement accuracy
Accuracy (digital measurement accuracy)
See Appendix 1: List of Input Sensor Types and Accuracy
Analog output accuracy
0.025% full scale
Long-term Drift
The first year is less than 0.2% of full scale
Temperature influence
See Appendix 2: Effects of Environmental Temperature
rated operation conditions
ambient temperature
-40~85℃ -20~60 ℃ (explosion-proof type)
condensation
allow
electromagnetic compatibility
GB/T 17626, three-level
Protection level according to EN 60529
IP67
design
casing
Aluminum die-casting parts
weight
1kg (excluding temperature sensor)
size
See Appendix 3: Dimensional Drawing of Two Wire Intelligent Temperature Transmitter
Cable sealing pipe connection thread
M20 × 1.5 Other threads require adapter
Sensor connection
Integrated
split type
Display and Control
Display Size
33×23mm
Display digits
5 people
Unit (switchable)
℃ or ℉
set an option
Three buttons on the panel or a HART handheld device and configuration software compatible with the HART protocol
power supply
15~36V DC
Electrical isolation
Ueff=1 kV, 50 Hz, 1 min between input and output
Certificates and approvals
Explosion proof type
ExdⅡCT6
Intrinsically safe type
ExiaⅡCT6