Welcome Customer !

Membership

Help

Baoying Jindi Power Equipment Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Products
Product Categories

Baoying Jindi Power Equipment Co., Ltd

  • E-mail

    Shbsdq@163.com

  • Phone

  • Address

    South Industrial Park, No. 8 Huaijiang Avenue, Baoying, Yangzhou City, Jiangsu Province

Contact Now

120KV/2mA DC High Voltage Generator

NegotiableUpdate on 11/28
Model
Nature of the Manufacturer
Producers
Product Category
Place of Origin

Overview

The DC high voltage generator is a new generation portable high voltage testing instrument designed and manufactured according to the Chinese power industry standard DL/T848.1-2004 "General Technical Conditions for High Voltage Test Equipment Part 1: DC High Voltage Generator", specifically used to test the electrical insulation strength and leakage current of power devices

Product Details

直流高压发生器

The DC high voltage generator is a new generation portable high voltage testing instrument designed and manufactured according to the Chinese power industry standard DL/T848.1-2004 "General Technical Conditions for High Voltage Test Equipment Part 1: DC High Voltage Generator", specifically used to test the electrical insulation strength and leakage current of power devices.

120KV/2mA DC High Voltage GeneratorBy using high-frequency voltage doubling circuit, advanced PWM pulse width modulation technology and voltage current dual loop feedback technology, the power supply adjustment rate and load adjustment rate are improved, resulting in high voltage stability and low ripple. Using imported high-power IGBT devices and their driving technology to eliminate switch interference and achieve high quality and portability of DC high-voltage generators. Selecting imported high-frequency and high-voltage rectifier diodes makes the voltage doubler more compact and lightweight, improving the overall efficiency of the machine. According to the theories of EMI electromagnetic interference and EMC electromagnetic compatibility, measures such as shielding, isolation, and grounding are adopted to enhance the safety of the entire machine and withstand rated voltage discharge without damage. The instrument has complete protection functions, including zero protection, overvoltage protection, overcurrent protection, and breakdown protection. The protection circuit uses nanosecond level dedicated sensors, which act quickly and reliably, effectively ensuring personal and equipment safety. The overvoltage setting uses a digital dip switch, which is easy to operate and has high setting accuracy. Add an intelligent high-precision 0.75U function button to facilitate the testing of zinc oxide lightning arresters.

This instrument adopts an integrated design scheme: the pressure doubling cylinder and the host are placed in the same chassis, combined with new technology and the use of new components, to achieve the advantages of small size, high power, light weight, easy operation, safety and reliability, and high power output quality. It is an ideal testing instrument in the high-voltage testing industry.

120KV/2mA DC High Voltage GeneratorSpecifications and main technical parameters

Specifications

Technical Specifications

60/2

100/2

120/2

160/2

180/2

200/2

250/2

100/200

3/2

200/300

5/2

other

Grade

Output voltage (kV)

60

100

120

160

180

200

250

100/200

200/300

600-800kV and other contracts

Customized.

Output current (mA)

2

2

2

2

2

2

2

3/2

5/2

Output power (W)

120

200

240

320

360

400

500

400

600

Charging current (mA)

3.0

3.0

3.0

3.0

3.0

3.0

3.0

4.5/3.0

7.5/3.0

Chassis weight (kg)

4.3

4.3

4.3

4.3

4.3

4.4

4.5

4.5

8.1

Height of pressure doubling cylinder (mm)

Φ80

×500

Φ80

×620

Φ80

×770

Φ80

×770

Φ110

×770

Φ110

×770

Φ110

×820

Φ110

×800

Φ110

×1350

Double pressure weight (kg)

6.3

6.8

6.8

7.2

7.2

7.2

7.6

7.5

12.6

High voltage polarity

Negative voltage polarity, zero voltage start, continuously adjustable.

working power supply

AC 220V±10%; 50Hz

Voltage measurement error

1.0% (full degree) ± 1 word, resolution 0.1% kV

Current measurement error

1.0% (full scale) ± 1 word, resolution 0.1% uA

Overvoltage setting error

≤1.0%

0.75 switching error

≤0.5%

ripple factor

≤1.0%

voltage stability

Random fluctuation, ≤ 0.5% when the power supply voltage changes by ± 10%

working method

Intermittent use; Rated load for 30 minutes; 1.1 times rated voltage usage: 10 minutes

ambient temperature

-15℃~50℃

relative humidity

When the temperature is 25 ℃, not more than 90% (no condensation)

altitude

Below 2500 meters