Welcome Customer !

Membership

Help

Yangzhou Lufeng Electric Co., Ltd
Custom manufacturer

Main Products:

instrumentb2b>Article

Yangzhou Lufeng Electric Co., Ltd

  • E-mail

    yzlufengdq@163.com

  • Phone

    13348124356

  • Address

    Yanyang Avenue, Industrial Concentration Zone, Liubao Town, Baoying County, Jiangsu Province

Contact Now
Technical specifications of cable type single channel partial discharge instrument
Date: 2025-12-19Read: 2

Product Features

After the partial discharge signal is digitized, a liquid crystal display is used to replace the traditional oscilloscope display.

The operation is the same as traditional analog partial discharge testing instruments, simple and easy to learn.

◆ Free selection of ellipse, line, and sine display modes

Adopting digital window opening technology can avoid interference affecting the measurement.

Open windows at any phase, choose single or double windows, and rotate the ellipse 150 degrees.

◆ It can freeze and save the current discharge map, and observe and analyze partial discharge pulses statically.

◆ The current discharge map can be saved to achieve traceability of test results.

Main technical indicators

1. The capacitance range of the testable product is 6PF to 250 μ F

2. Calibration pulse generator:

Correction of square wave voltage amplitude: 20Mv~1V (divided into 6 levels)

Correction square wave voltage front: ≤ 100ns

Correction of square wave voltage tail: ≥ 100us

The quantitative range of discharge capacity (high-voltage injection capacitance of 100Pf) is: 2, 5, 10, 20, 50, 100Pc

3. Amplifier frequency band:

① Low end: 10KHZ, 20KHZ, 40KHZ optional

②: 80KHZ、200KHZ、300KHZ 任选

4. Amplifier gain adjustment:

Roughly adjust to six levels, with a gain of 20 ± 1 between levelsDb; fine tuning range ≥ 20db.

5. Time window:

① Window width: adjustable range of 15 ° to 150 °;

② Window position: Each window can rotate 0 ° to 170 °;

③ Two time windows can be opened separately or simultaneously.

6. Discharge gauge:

Digital header: displayed on a 3 1/2 LED digital meter

0-100.<± 5% (based on full scale)

7. Elliptical Time Base:

①频率50 HZ、100HZ、150HZ、200HZ、400HZ。

② Elliptical rotation: With 30 ° as the first gear, it can rotate 150 °.

③ Display mode: ellipse line sine.

8. Test voltmeter:

① Range: 100KV (expandable)

② Display: 3 1/2 digital voltmeter indication

Accuracy: better than ± 5% (measured at full scale)

9. Equipped with zero mark function, it is conducive to the identification of partial discharge

10. Volume: 450 * 380 * 220 (width * depth * height) mm3

11. Weight: Approximately 15kg.