-
Fault manifestationThe temperature difference between different areas inside the box exceeds ± 2 ℃, which affects the consistency of the test.
-
Possible reasons:
- Dust accumulation or blockage of debris in the air duct can cause poor airflow circulation.
- The fan impeller is worn or the belt is loose, and the speed is insufficient.
- Abnormal switching of cold and hot air doors, uneven mixing of cold and hot airflow.
-
maintenance measures:
- Remove the air duct baffle, clean the dust and foreign objects with compressed air.
- Check the tension of the fan belt and replace it if it is severely worn; The dust accumulation on the impeller needs to be cleaned with neutral detergent.
- Debug the air door drive motor, check if the solenoid valve is stuck, and replace the seal if necessary.
-
Fault manifestationWhen setting a high temperature (such as 150 ℃), the heating rate is lower than 0.5 ℃/min or cannot reach the set value.
-
Possible reasons:
- Scaling on the surface of the heating tube or partial melting of the resistance wire results in a decrease in heating power.
- Solid state relay contacts oxidize, resulting in insufficient current output.
- Temperature control instrument parameters drift and PID adjustment abnormality.
-
maintenance measures:
- After cutting off the power, disassemble the heating tube, use sandpaper to polish the surface scale, measure the resistance value, and replace the damaged heating tube as a whole.
- Replace the solid-state relay or wipe the contact oxide layer with alcohol.
- Re calibrate the temperature control instrument and input the default PID parameters provided by the manufacturer (such as P=15%, I=30s, D=10s).
-
Fault manifestationThe arrival time of low temperature (such as -40 ℃) exceeds the rated value, or the temperature fluctuates greatly.
-
Possible reasons:
- Refrigerant leakage (common at copper pipe welds) and insufficient system pressure.
- Poor heat dissipation of the condenser, dust accumulation on the fins, or fan shutdown.
- The dry filter is clogged, resulting in restricted refrigerant flow.
-
maintenance measures:
- Use a halogen leak detector to detect leaks, vacuum after welding, and fill with refrigerant such as R404A according to the manufacturer's specified amount.
- Clean the dust on the condenser fins with a brush every week, check if the fan capacitor is faulty, and replace damaged parts.
- Replace the dry filter and, if necessary, also replace the expansion valve.
-
Fault manifestationTouch screen displays garbled code, program interruption or alarm codes (such as E01, E03).
-
Possible reasons:
- The power supply voltage fluctuates by more than ± 10%, causing damage to the control board components.
- The wiring of the temperature sensor (PT100) is loose or the probe is damp and malfunctioning.
- PLC program errors are often caused by misoperation or electromagnetic interference.
-
maintenance measures:
- Configure a voltage regulator, check the fuses and capacitors on the control board, and replace burnt out components.
- Re weld the sensor wiring, seal the probe with silicone or replace it with a new sensor when it becomes damp.
- Contact the manufacturer's technical personnel to remotely refresh the PLC program, or install anti-interference magnetic rings in the control box.
-
Daily check:
- Observe the operating current of the compressor (normal range 10-15A) and the pressure on the high and low pressure gauges (high pressure 1.2-1.8MPa, low pressure 0.2-0.4MPa).
- Wipe the outer wall of the box and the glass observation window to avoid residual corrosive gases.
-
Weekly maintenance:
- Use a soft cloth dipped in neutral detergent to wipe the inner chamber of the box and remove any residual condensed water or volatile substances from the test sample.
- Check the sealing performance of the door seal, and replace it promptly if it ages or deforms to prevent loss of cooling capacity.
-
Monthly projects:
- Clean the cooling fan grille of the refrigeration system and use compressed air to blow away dust inside the control box.
- Calibrate temperature uniformity: Place 3 standard thermometers and compare the displayed values after running the temperature cycle. If the deviation exceeds ± 1 ℃, it needs to be adjusted.
-
Quarterly projects:
- Check the tightness of the heating tube wiring terminals and apply thermal conductive silicone grease to prevent poor contact.
- Add high-temperature resistant lubricating grease (such as molybdenum disulfide grease) to rotating components such as fans and air door drive motors.
- If the suspension exceeds 15 days, you need to:
- Drain the accumulated water in the box and open the box door for ventilation for 24 hours to prevent mold growth.
- Disconnect the main power supply, place moisture-proof agent inside the control box, and cover the equipment with a dust cover.
- Power on once a month (no-load) for 2 hours each time to maintain the flow of compressor lubricating oil.
- Before maintenance, the power must be cut off, and protective gloves should be worn during refrigeration system maintenance to avoid refrigerant frostbite.
- Non professionals are prohibited from disassembling high-pressure components such as heating tubes and compressors. Operations involving refrigerants must be completed by certified personnel.
- Establish equipment maintenance records, including fault handling time, component replacement models, and calibration data, to facilitate traceability of equipment performance changes.
Through standardized troubleshooting and periodic maintenance, the failure rate of the thermal shock test chamber can be effectively reduced, ensuring the stability of the temperature simulation environment and the accuracy of the test data.